# Installation des joints de démontage près des vannes\n\n## Guide pour acheteurs B2B\n\nCet article aide les acheteurs techniques, installateurs, distributeurs et clients OEM/ODM à préparer les informations nécessaires avant une demande de prix.\n\n## Raccords de tuyauterie: Installation des joints de démontage près des vannes\n\nNe choisissez pas seulement par nom de produit. Vérifiez la dimension, la pression, la norme de raccordement, le matériau, le fluide, la température, la position de montage, la quantité et le plan.\n\nLes produits concernés peuvent inclure joints de dilatation en caoutchouc, joints de démontage, raccords de tuyauterie, adaptateurs à bride, compensateurs métalliques et manchons étanches.\n\n## RFQ\n\nPour un devis plus rapide, envoyez DN, pression, norme de bride, matériau, fluide, température, quantité, plan ou photo.\n\n- DN / size\n- pressure rating\n- connection standard\n- material\n- working medium and temperature\n- quantity\n- drawing, photo or specification\n\n## Quality and Packing\n\nAvant expédition, vérifiez l’aspect, les dimensions, les faces de raccordement, les accessoires, l’étiquetage et l’emballage. Les essais doivent être confirmés avant production.\n\n## Project Inquiry\n\nPour votre projet, envoyez dimensions, pression, norme de raccordement, matériau, fluide, quantité et plan afin de confirmer la configuration.

常见问题

?Should a dismantling joint be installed upstream or downstream of a valve?

There is no universal position. The location should be selected according to the maintenance direction, piping layout, lifting access, flow arrangement, pipe anchors and approved project drawings. The joint must provide usable removal clearance, while the valve and pipeline remain independently supported.

?Can a dismantling joint correct lateral pipe misalignment?

No. A dismantling joint mainly provides controlled axial installation adjustment. It should not be used to force significantly misaligned, angled or non-parallel flanges into position.

?Are flange gaskets required when installing a dismantling joint?

Suitable flange gaskets are normally required between the valve, dismantling joint and pipeline flanges. Their material must match the medium, temperature, pressure and flange face. Confirm whether they are included in the ordered supply scope.

?Can a dismantling joint support valve or pipe weight?Can a dismantling joint support valve or pipe weight?

No. Valves, pipes and the joint must be properly supported by foundations, supports, hangers or lifting equipment. The dismantling joint should not be used as a load-bearing component.

?What is the difference between flange bolts, gland bolts and tie rods?

Flange bolts connect the valve, joint and pipe flanges. Gland bolts compress the sealing ring around the telescopic section. Tie rods restrain the assembly and transmit approved axial forces. They have different functions and must be adjusted according to the product drawing.Flange bolts connect the valve, joint and pipe flanges. Gland bolts compress the sealing ring around the telescopic section. Tie rods restrain the assembly and transmit approved axial forces. They have different functions and must be adjusted according to the product drawing.

?What must be done before using the joint to remove a valve?

Shut down and isolate the pipeline, fully depressurize and drain it, support the valve and adjacent pipe independently, and then release and collapse the joint according to the approved installation instructions. Never adjust or dismantle the joint under pressure.